Posted by skhorleb on 08/21/2005 03:15 PM

Every time I connect the computer to the M1G control, I get a message that says that the texts and rules are out of synch. To eliminate the conflict, I send the texts and rules to the control from the computer. This message and synchronization step must be taken every time I connect the two, regardless if any changes have actually been made via the EKRP or not. I am not aware of any changes to the control configuration between connect sessions using the keypads. Any ideas what the underlying problem is that leads to the control to become out of step with the EKRP? Thank you in advance for any advice.

Re: Texts and Rules synchronization
Posted by DubG on 01/06/2011 01:25 AM

I am having the same issue and it is REALLY annoying...

Re: Texts and Rules synchronization
Posted by bradweeks on 01/06/2011 08:26 AM

Create a New Default Account and Receive the information from the system
Click File New Account
Assign a New ID Name
Select System Type M1G or EZ8
Enter the Serial Number
Enter the RP Access Code
Check the Default Account button and select the Firmware version which is currently running in the system 5.x.x OR 4.x.x
Click OK
Connect to the system
Click the Send/Rcv Icon and "RECEIVE ALL"
Save the file
Disconnect and then reconnect to see if you still have the Conflict

Edited by bradweeks on 01/06/2011 08:27 AM